Safety & Warnings
Handle with care and inspect regularly to ensure the product is in good working order.
If this product, power supply cord or plug shows any signs of damage: stop use, unplug the product and contact Kogan.com support.
- Read all instructions before using the appliance and retain for reference.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
- This appliance is designed for consumer use: follow directions and use only as described.
- Install, use, repair and store only in a room larger than 5m2.
- Do not attempt to defrost any components of the unit by accelerated means such as hot water.
- Do not pierce or otherwise damage the piping.
- The air conditioner must be installed with a stop valve cover.
- Note that refrigerant may be tasteless.
- Turn the power off during storms and before cleaning or maintenance
- The air conditioner must be grounded. Incomplete grounding may result in electric shocks.
- Always switch off the device and cut the power supply when the unit will not be used for a long time.
- Don't allow water to contact the product or remote control or touch it with wet hands.
- Do not operate the unit if it has been dropped.
- Do not clean with water or corrosive liquids.
- Do not put hands or any other objects into the air inlets/outlets or allow them to be blocked.
- Ensure stand is secure.
- Do not allow the air conditioner to blow against heaters.
- Do not put weight on the outdoor unit.
- If your air conditioner is permanently connected to fixed wiring, an anti-explosion residual current device (RCD) with rated residual operating current within 30 mA should be installed in the fixed wiring.
- This appliance contains no user-serviceable parts. If it suffers any failure or damage, cease usage and contact Kogan Support after consulting the Troubleshooting section of this manual.
Overview
Indoor Unit
Remote controller functions detailed in Operation.
Outdoor Unit
NOTE: The above diagrams are for illustration purposes only and may differ from the final product.
Important Notes:
- Your unit will require connecting pipes which do not come with your product. These pipes are intended to be supplied and installed by professional installers.
- The fan will not start running immediately after heating has started to avoid blowing cool air.
- When the weather is sufficiently cold and wet, the outdoor unit may frost over. The air conditioner will start the defrost function automatically and stop heating, usually for 5-12 minutes. During this time, vapour may come out of the outdoor unit: this is normal. When defrosting is complete, heating will resume.
- When the air conditioner is turned off, the main controller will determine whether to stop immediately or to first run in low power for a short time.
Operation
Product functions are controlled by the remote controller.
- Before first use, install batteries and ensure the "+” and "-" poles are correctly positioned.
- Ensure the remote controller is pointed towards the air conditioner without obstructions and a maximum distance of 8m.
- Do not drop or damage the remote controller.
- Do not let any liquid in the remote controller.
- Do not expose the remote controller directly to sunlight or excessive heat.
- If the remote controller does not function normally, remove batteries for 30 seconds before reinstalling. If it does not work, replace batteries.
- Do not mix new and old batteries.
- Remove the batteries if not using for a long time.
- Dispose of batteries properly.
Battery replacement.
Remote Control Functions
Number | Display Panel | Description |
1. | ON/OFF |
|
2. |
Speed |
|
3. |
Display |
|
4. |
iFEEL |
|
5. |
Timer |
|
6. |
iCLEAN |
|
7. |
Up and Down (Set) |
|
8. |
Turbo |
|
9. |
Mode |
|
10. |
Sleep |
|
11. |
Swing |
|
12. |
Anti-F |
|
Automatic Operation Mode
- Press the “MODE” button to select the automatic operation mode.
- Press the “SPEED” button to select the fan speed from LOW, MID, HIGH, AUTO.
- Press the “ON/OFF” button to begin operation.
- Press the “ON/OFF” button again to stop the air-conditioner.
Note: Temperature cannot be set / will not take effect in fan operation mode.
Cooling / Heating Mode
- Press the “MODE” button to select Cooling/Heating mode.
- Set the temperature with the up and down buttons.
- Press the "SPEED” button to select the fan speed from LOW, MID, HIGH, AUTO.
- Press the "ON/OFF” button to begin operation.
- Press the "ON/OFF” button again to stop the air-conditioner.
Fan Operation Mode
- Press the “MODE” button to select the fan operation mode.
- Press the “SPEED” button to select the fan speed from LOW, MID, HIGH, AUTO.
- Press the “ON/OFF” button to begin operation.
- Press the “ON/OFF” button again to stop the air-conditioner.
Note: Temperature cannot be set / will not take effect in fan operation mode.
Drying Operation Mode
- Press the "MODE” button to select the drying operation mode.
- Set the temperature with the up and down buttons.
- Press the "SPEED” button to select the fan speed from LOW, MID, HIGH, AUTO.
- Press the "ON/OFF” button to begin operation.
- Press the "ON/OFF” button again to stop the air-conditioner.
Note: Temperature cannot be set / will not take effect in fan operation mode.
Cleaning & Care
Warnings
- Shut down the air conditioner and leave off for 5 minutes before cleaning.
- Do not use volatile liquids such as thinner or gasoline. Do not allow the interior of the air conditioner to become wet.
- Pay attention to the state of the filter. If it becomes clogged with dust, this can adversely affect product function.
- After removing the filter, do not touch the fin part of the indoor unit or exert any force on the refrigerant pipeline.
Cleaning Panel
Clean panel surface with a soft dry cloth or a damp cloth moistened with a neutral detergent. Do not remove the panel and take care that water does not get in the product.
Cleaning the Air Filter
- Remove the air filter by opening the panel with both hands and pulling the filter out downwards.
Use a vacuum cleaner or water to rinse filter. If it is very dirty, dissolve a mild detergent into warm water (below 45°C). - Allow the filter to dry fully by air.
- Reinstall by following removal steps in reverse.
Before Use
- Ensure air inlets and outlets are unblocked.
- Ensure there is no blockage in the water outlet of the drain pipe.
- Ensure the ground wire is reliably grounded.
- Ensure batteries are installed in the remote control and have sufficient power.
- Ensure the outdoor unit mounting bracket is undamaged. If there is, contact Kogan.com.
After Use
- Turn off the power and remove batteries from the remote control.
- Clean filter and unit body.
- Remove dust and debris from the outdoor unit.
Troubleshooting
Issue |
Possible Cause |
Steps to Resolve |
Not turning on |
Power outage, blown fuse, loose power plug |
Check power and retry |
ON timer set |
Wait or cancel the timer setting |
|
Does not run after being turned off and on on |
Expected function: protective switch will delay operation for 3-5 minutes after being powered off |
|
Stops running after a while |
Set temperature reached |
Expected function |
Defrosting |
Will resume automatically |
|
Shutdown timer set |
Check and resume |
|
Cooling/heating ineffective |
Dust or blockage |
Check and clear |
Windows/doors opened, blocked exhaust fan |
Check and resume |
|
Incorrect mode setting |
Check mode and temperature |
|
Odour produced |
Environmental issue |
Check environment |
Mould buildup |
Activate cleaning function |
|
Sound of running water |
Flow of refrigerant |
Expected function |
Click at startup/shutdown |
Thermal expansion/contraction of unit parts |
Expected function |
Abnormal sound |
Fan, compressor switched on/off |
Wait |
Sound from defrosting |
Expected function |
|
Dust or blockage |
Check and clear |
|
Drops of water on the surface of the indoor unit |
Ambient humidity high |
Expected function |
Prolonged cooling in open space |
Close windows/doors |
|
The angle of louvre blades too small |
Increase angle of louvre blades |
|
The mist produced during cooling |
Can occur with high temperature and humidity |
Expected function |
The Air Conditioner initially turns on, but then slowly it turns down until it turns off. |
The filters are blocked. |
Manually clean the filters of your Air Conditioner. |
Installation Guide
Notices Before Installation
- This unit must only be installed, moved or uninstalled by an authorised service centre according to national safety and electrical requirements and this manual
- Refrigerant leak tests must be made after installation.
- When installing or repairing: if the connecting line is not long enough, the entire connecting line must be replaced and not extended.
Unpacking
- Open the box and check the air conditioner in an area with good ventilation. Open the door and window. Operators must wear anti-static devices.
- A professional must determine whether there is refrigerant leakage before opening the outdoor unit box.
- Fire prevention and anti-static devices must be installed before checking.
- Ignition sources, smoking and calling must not take place in an area where R32 refrigerant is located.
- Keep leak detector in working state during installation.
- If leakage occurs, resolve it immediately.
- Keep electric appliances, power switches, plugs, sockets, high-temperature heat sources and high static away from the area underneath the indoor unit’s sidelines.
- Install in a location accessible for maintenance.
Installation Position Requirements
- Avoid positions with inflammable or explosive gas leakage or where there are strongly aggressive gases.
- Avoid places subject to strong artificial electric/magnetic fields.
- Avoid places subject to noise and resonance.
- Avoid severe natural conditions (e.g. heavy lampblack, strong sandy wind, direct sunshine or high-temperature heat sources)
- Avoid places within the reach of children.
- Shorten the connection between the indoor and outdoor units.
- Do not install the outdoor unit in any way that could occupy an aisle, stairway, exit, fire escape, catwalk or any other public area.
- Install the outdoor unit as far as possible from the doors and windows of the neighbours as well as green plants.
Installation Environment Inspection
- Check nameplate of the outdoor unit to ensure the refrigerant is R32.
- Check the floor space of the room, it should not be less than usable space (sm2) in the specification. Install the outdoor unit in a well-ventilated place.
- Check the surrounding environment of installation site: R32 shall not be installed in the enclosed reserved space of a building.
- When using an electric drill to make holes in the wall, check first whether there is an existing pipeline for water, electricity and gas. It is suggested to use the reserved hole in the roof of the wall.
Mounting Structure
- The mounting rack must meet the relevant national or industrial standards in ferms of strength with welding and connection areas rustproofed.
- The mounting rack and its load carry surface shall be able to withstand 4 times or above the weight of the unit, or 2OOkg, whichever is heavier.
- Fasten the mounting rack of the outdoor unit with an expansion bolt.
- Ensure installation is secure regardless of what type of wall on which it is installed, to prevent potential dropping that could hurt people.
Electrical Safety Requirements
- Be sure to use the rated voltage and air conditioners dedicated circuit for the power supply, and the power cord diameter must meet the national requirements.
- When the maximum current of an air conditioner is ≥16A, it must use the air switch or leakage protection switch equipped with protection devices.
- The operating range is 90%-110% of the local rated voltage. But insufficient power supply malfunction, electrical shock, or fire. If the voltage instability proposed to increase the voltage regulator.
- The minimum clearance between the air conditioner and the combustibles is 1.5 m.
- The interconnection cord connects the indoor and outdoor units. You must first choose the right cable size before preparing it for connection.
- Cable Types: Outdoor Power Cable - H07RN-F or H05RN-F; Interconnection cord - H07RN-F or H05RN-F;
- Minimum Cross-Sectional Area of Power cable and interconnection cord.
- The size of the interconnection cord, power cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.
- Note: Core number of cable refers to the detailed wiring diagram adhered on the unit which you purchased.
Raised Height Operation Requirements
- When carrying out the installation at 2m or higher above the base level, safety belts must be worn and ropes of sufficient strength are securely fastened to the outdoor unit, to prevent falling that could cause personal injury or death as well as property loss.
Grounding Requirements
- The air conditioner is the class I electrical appliance and must ensure a reliable grounding.
- Do not connect the grounding wire to a gas pipe, water pipe, lightning rod, telephone line, or a circuit poorly grounded to the earth.
- The grounding wire is specially designed and shall not be used for other purposes, nor shall it be fastened with a common tapping screw.
- Interconnection cord diameter should be recommended as per instruction manual, and with type O terminal that meet local standards (internal diameter of type O terminal needs to match the screw size of the unit, no more than 4.2mm). After installation, check the screws whether have been fixed effectively, and there is no risk of loosening.
Other
- The connection method of the air conditioner and the power cord and the interconnection method of each independent element shall be subject to the wiring diagram affixed to the machine.
- The model and rating value of the fuse shall be subject to the silkscreen on the corresponding controller or fuse sleeve.
Included Parts & Accessories
Included Parts in the Indoor Unit
Name | Quantity |
Indoor Unit | 1 |
Remote Controller | 1 |
Batteries | 2 |
User Manual | 1 |
Darin Pipe | 1 |
Included Parts in the Outdoor Unit
Name | Quantity |
Outdoor Unit | 1 |
Pipe Protection Ring | 1 |
Luting (putty) | 1 |
NOTE: There may be minor differences in the included parts.
Refrigerant piping size
Model | The diameter of the Inlet Copper Pipe (mm) | The diameter of the Outlet Copper Pipe (mm) | Standard Pipe Length (m) | Max Pipe Length (m) | Max Installation Fall | Stop Valve Outlet Connector Diameter (mm) |
KASSAC26R3A | 6/6.35 | 9.52 | 3.6 | 20 | 10 | 6/6.35 |
KASSAC52R3A | 6/6.35 | 16 | 3.6 | 20 | 15 | 9.52 |
Indoor Unit Installation
Mounting plate | |
|
|
Wall-through Hole | |
Note: Usually, the wall hole is Ø60mm~Ø80mm. Avoid pre-buried power wire and hard wall when making the hole. |
![]() |
Route of Pipeline | |
|
|
![]() |
![]() |
Drainpipe connection |
Note: Carefully check if there is any damage of joints before installation. The joints shall not be reused, unless after re-flaring the pipe. |
![]() |
Wrap the Piping |
|
![]() |
Fixing the Indoor Unit | |
|
![]() |
Wiring diagram |
After installation, check:
|
![]() |
Note: Depending on product revision, minor differences in wiring may exist, detailed on the diagram adhered to the product.
![]() |
Install the connection pipe |
![]() |
Outdoor Unit Installation
Wiring Connection | |
|
![]() |
Wiring diagram |
![]() |
Note: Depending on product revision, minor differences in wiring may exist, detailed on the diagram adhered to the product.
Vacuuming |
|
★ Exclusive R32 refrigerant pump must be used in making R32 refrigerant vacuum. Before working on the air conditioner, remove the cover of the stop valve (gas and liquid valves) and be sure to retighten it afterwards (to prevent the potential air leakage)
|
![]() |
Optional: Outdoor condensation drainage (Heat pump type only) | |
When the unit is heating, the condensing water and defrosting water can be out reliably through the drain hose. Installation: Install the outdoor drain elbow (not included) in Ø25 hole on the base plate, and join the drain hose to the elbow so that the wastewater formed in the outdoor unit can be drained out to a proper plate. |
![]() |
Post-Installation
Check After Installation |
★ Electrical Safety Check
★ Installation Safety Check
★ Leak test of the refrigerant Depending on the installation method, the following methods may be used to check for suspect leak, on areas such as the four connections of the outdoor unit and the cores of the cut-off valves and t-valves:
Note: Make sure that the ventilation is good before checking. |
Test Operation |
Test Operation preparation:
Note: Make sure that the ventilation is good before testing. Test Operation method:
|
Maintenance
See safety and warnings section.
Qualification Requirements of Maintenance Personnel |
|
Inspection of the Site |
Safety inspection must be taken before maintaining equipment with R32 refrigerant to make sure the risk of fire is minimized. Check whether the place is well ventilated, whether anti-static and fire prevention equipment is perfect. While maintaining the refrigeration system, observe the following precautions before operating the system. |
Operating Procedures |
1. General work area: 2. Checking for presence of refrigerant: 3. Presence of fire extinguisher: 4. No ignition sources: 5. Ventilated Area(open the door and window): 6. Checks to the refrigeration equipment: 7. Checks to electrical devices: |
Inspection of Cable |
Check the cable for wear, corrosion, overvoltage, vibration and check if there are sharp edges and other adverse effects in the surrounding environment. During the inspection, the impact of aging or the continuous vibration of the compressor and the fan on it should be taken into consideration. |
Leakage check of R32 refrigerant |
Note: Check the leakage of the refrigerant in an environment where there is no potential ignition source. No halogen probe (or any other detector that uses an open flame) should be used. |
Removal and Vacuum Pumping |
1. Make sure there is no ignited fire source near the outlet of the vacuum pump and the ventilation is well. 2. Allow the maintenance and other operations of the refrigeration circuit should be carried out according to the general procedure, but the following best operations that the flammability is already taken into consideration are the key. You should follow the following procedures: • Remove the refrigerant. • Decontaminate the pipeline by inert gases. • Evacuation. • Decontaminate the pipeline by inert gases again. • Cut or weld the pipeline. 3. The refrigerant should be returned to the appropriate storage tank. The system should be blown with oxygen-free nitrogen to ensure safety. This process may need to be repeated for several times. This operation shall not be carried out using compressed air or oxygen. Through the blowing process, the system is charged into the anaerobic nitrogen to reach the working pressure under the vacuum state, then the oxygen-free nitrogen is emitted to the atmosphere, and in the end, vacuumize the system. Repeat this process until all refrigerants in the system is cleared. After the final charging of the anaerobic nitrogen, discharge the gas into the atmosphere pressure, and then the system can be welded. This operation is necessary for welding the pipeline. |
Procedures of Charging Refrigerants |
As a supplement to the general procedure, the following requirements need to be added: - Make sure that there is no contamination among different refrigerants when using a refrigerant charging device. The pipeline for charging refrigerants should be as short as possible to reduce the residual of refrigerants in it. - Storage tanks should remain vertically up. - Make sure the grounding solutions are already taken before the refrigeration system is charged with refrigerants. - After finishing the charging (or when it is not yet finished), label the mark on the system. - Be careful not to overcharge refrigerants. |
Scrap and Recovery |
Scrap: Recovery: |